The NF lighting and power distribution panelboard offers a wide selection of circuit breakers, accessories, and ready-to-install kits, as well as 200% rated neutrals for non-linear loads.

Standard Panelboard Features

  • 480Y/277Vac maximum
  • 600 Amp maximum main circuit breaker or main lugs
  • 18K thru 200K SCCR
  • Fully rated 480Y/277 Volts, 18K/35K/65K AIR
  • Main and sub-feed circuit breakers are hard bussed and vertically mounted
  • 125 Amp maximum branch mounted circuit breakers
Schneider Electric NF Lighting Panelboards
  • Interiors are field convertible to top or bottom feed
  • Modular construction to accept field installable sub-feed lugs, thru-feed lugs, and sub-feed breakers
  • Circuit breakers are HACR, SWD, and HID rated
  • Ready-to-install main circuit breaker kits convert main lug interiors
  • VISI-TRIP® indication on branch circuit breakers
  • Suitable for use as service equipment
  • Complete line of UL Listed interiors with 200% rated neutrals for non-linear loads

 

800 A NF Main Lug Panelboards with 400 A Sub Feed Circuit Breakers

  • Fully assembled 800 A version of NF main lug panelboards
  • NEMA 1 , 3R, 5 and 12 enclosures
  • 400 A sub-feed CB capability available for 600 A and 800 A NF panelboards
  • 600 A and 800 A MLO panelboards (one 400 A LA or LH sub-feed CB may be used with one 250 A KA or KH CB
  • 400 A LC sub-feed CB (250 A KC sub-feed CB cannot be combined with the LC)

Column-Width Panelboard Features

Column-width panelboards are designed to fit into a standard size W, H, or I-beam support column in industrial plants.

  • 240Vac maximum or 480Y/277Vac maximum
  • Copper bus standard
  • 225 Amp maximum main circuit breaker or main lugs
  • 60 Amp maximum branch circuit breaker
  • Suitable for use as service equipment when using main circuit breaker with 30 or 42 circuits
  • Top or bottom feed interiors
  • Accepts plug-on or bolt-on branch circuit breakers
  • Solid neutral located on same end as mains